STANDARD FEATURES:Compact & vermin proof design.
- No fire hazard.
- Long Electrical & Mechanical life.
- Compartmentalized construction.
- Incorporates reliable vacuum technology for switching.
- Antipumping scheme.
- Suitable and tested for rapid autoreclosing duty.
- Earthed truck for earthing bus or line.
- Withdrawable or fixed PT (Bus or Line).
- Earthed metallic shutters with unique integral device for retaining the dead section shutter in open position and restoring usual automatic features by insertion of breaker truck.
- Double Busbar system for continuous bus rating up to 2000A and switching by single off load isolator of 1250 A continuous current rating – Ideal for process industries.
- Ideal and tested for capacitive current breaking application.
Safety interlocks to prevent:-
- Insertion of circuit breaker in ‘CLOSED ‘condition.
- Withdrawal of circuit breaker when it is in ‘closed’ condition. (Built in mechanical interlock can be unlocked only after tripping of breaker)
- Operation of circuit breaker in any position other than ‘ISOLATED‘ or ‘TEST’ or ‘SERVICE’ positions.
OPTIONAL FEATURES:
- Double Busbar system with switching through circuit breakers with horizontal or vertical duplicate breaker chambers, to ensure continuous supply on load side.
- Self aligning control circuit plugs and socket arrangement. Automatic engagement before ‘TEST’ position while racking in and disengagement after ‘TEST’ position while racking out.
- Single convertible circuit breaker truck for earthing line or Bus.
- Integral earthing switch (for line earthing only) capable of carrying full fault current.
- 95kVp Impulse level for continuous current rating up to 1250 A for circuit breaker and panel.
- Series tripping facility.
- Emergency tripping facility (without opening front door)
- CTD for automatic tripping of circuit breaker in the event of failure of control supply.
- Maximum continuous current rating of 2000A for Incomer and Bus Coupler breakers and 1250 A for feeder breakers.
RATING:
• Rated Voltage ( kV ) : 11
• Rated Insulation level (kV/kVp) : 28 /75*
• Rated frequency (Hz) : 50
• Rated normal current : 630 / 1250 / 2000
• Rated short time current (kA) for Duration (sec) : 26.24 for 3
• Rated peak withstand current (kA) : 66
• Rated operating sequence : O-0.3sec-CO-3min-CO
• Rated control voltage DC (V) : 24 to 220 **
• Rated auxiliary voltage AC (V) : 230